Products > E1FW Cable Gland
explosive atmosphere double seal for all types of steel & aluminium wire armoured cables

E1FW Cable Gland
explosive atmosphere double seal for all types of steel & aluminium wire armoured cables

Globally Approved, Explosive Atmosphere Cable Gland

• Metal-to-metal armour clamping
• Direct & remote installation
• Displacement type flameproof inner seal
• Controlled outer ‘load retention’ seal
• Unique OSTG prevents overtightening
• Designed to prevent Coldflow, see CMP Technical Document TS001
• -60°C to +130°C
• Class I Zone 1, 21 and Zone 2, 22 Class I Division 2 ABCD
• Globally marked, IECEx, ATEX & cCSAus
• EMC tested

For under / oversized armour wires

For all types of Steel & Aluminium Wire Armoured Cables

Description

Technical

Design Specification BS 6121:Part 1:1989, IEC 62444, EN 62444
Mechanical Classifications* Impact = Level 8, Retention = Class D
Enclosure Protection IK10 to IEC 62262 (20 joules) Brass & Stainless Steel only
Electrical Classifications * Category B
ATEX Certificate SIRA13ATEX1071X, SIRA13ATEX4077X
Code of Protection II 2G, II 1D, Ex d IIC Gb, Ex e IIC Gb, Ex ta IIIC Da
II 3G Ex nR IIC Gc, IM2 Ex d I Mb, Ex e I Mb
Compliance Standards EN 60079-0,1,7,15,31
IECEx Certificate IECEx SIR 13.0026X, IECEx SIM 14.0007X
Code of Protection Ex d IIC Gb, Ex e IIC Gb, Ex nR IIC Gc, Ex ta IIIC Da, Ex d I Mb, Ex e I Mb
Compliance Standards IEC 60079-0,1,7,15,31
cCSAus Certificate 1310517
Code of Protection Ex d IIC; Ex e II; Ex nR II; Class I, Div 2, Groups A,B,C,D, Class II, Div 2 Groups E,F,G, Class
III, Encl Type T4X Class I, Zone 1, AEx e II / AEx nR II
Compliance Standards CAN/CSA-C22.2 No 0,18,25,30,174,94, CAN/CSA-E60079-0,1,7,15
ANSI/UL 514B Ed 5, ANSI/UL 50 Ed 11, ANSI/UL 2225 Ed 4, UL60079-0,1,7,15
EAC Certificate (Formerly GOST R, K & B) C-GB.AA87.B.00487
KCC Certificate 14-GA4BO-0257X
CCOE / PESO (India) Certificate P333688
NEPSI Certificate GYJ13.1140X , GYJ13.1282X
INMETRO Approval TÜV 12.0618X
RETIE Approval 03866
Marine Approvals LRS: 01/00172, DNV: E-13848, ABS: 14-LD234401A-4-PDA, BV: 43180/A1BV
Ingress Protection Rating ** IP66 as standard (IP67, IP68 available upon request)
Deluge Protection Compliance DTS01:91 option available on request (white ferrule for identification purposes)
Cable Gland Material Brass, Electroless Nickel Plated Brass, Aluminium
Seal Material CMP SOLO LSF Halogen Free Thermoset Elastomer
Cable Type Single Wire Armour (SWA), Aluminium Wire Armour (AWA)
Armour Clamping Detachable Armour Cone & AnyWay Universal Clamping Ring
Sealing Technique CMP Inner Displacement Seal & Unique CMP ‘LRS’ ™ Outer Load Retention Seal
Sealing Area(s) Cable Inner Bedding & Outer Cable Sheath
Optional Accessories Locknuts, Earth Tags, Serrated Washers, Entry Thread Seals, Shrouds,Ingress Discs
Optional Installation Tools Spanners, Armour Former Tool

Product Table

Metric

Cable Gland Size Available Entry Threads “C” (Alternate Metric Thread Lengths Available) Cable Bedding Diameter “A” Overall
Cable
Diameter
“B”
Armour Range Across
Flats
“D”
Across
Corners
“D”
Protrusion
Length “F”
Combined Ordering Reference
(*Brass Metric)
Shroud Cable
Gland
Weight
(Kgs)
Standard Option
Metric Thread Length (Metric) “E” NPT Thread Length
(NPT) “E”
NPT Min Max Min Max Min Max Max Max Size Type Ordering
Suffix
20S16 M20 15.0 ½” 19.9 ¾” 3.1 8.6 6.1 13.1 0.8 1.3 24.0 26.4 72.5 20S16 E1FW 1RA PVC04 0.16
20S M20 15.0 ½” 19.9 ¾” 6.1 11.6 9.5 15.9 0.8 1.3 24.0 26.4 70.0 20S E1FW 1RA PVC04 0.15
20 M20 15.0 ½” 19.9 ¾” 6.5 13.9 12.5 20.9 0.8 1.3 30.5 33.6 73.0 20 E1FW 1RA PVC06 0.21
25S M25 15.0 ¾” 20.2 1″ 11.1 19.9 14.0 22.0 1.3 1.6 37.5 41.3 89.0 25S E1FW 1RA PVC09 0.33
25 M25 15.0 ¾” 20.2 1″ 11.1 19.9 18.2 26.2 1.3 1.6 37.5 41.3 89.0 25 E1FW 1RA PVC09 0.33
32 M32 15.0 1″ 25.0 1 ¼” 17.0 26.2 23.7 33.9 1.6 2.0 46.0 50.6 86.0 32 E1FW 1RA PVC11 0.43
40 M40 15.0 1 ¼” 25.6 1 ½” 22.0 32.1 27.9 40.4 1.6 2.0 55.0 60.5 90.0 40 E1FW 1RA PVC15 0.62
50S M50 15.0 1 ½” 26.1 2″ 29.5 38.1 35.2 46.7 2.0 2.5 60.0 66.0 91.0 50S E1FW 1RA PVC18 0.75
50 M50 15.0 2″ 26.9 2 ½” 35.6 44.0 40.4 53.0 2.0 2.5 70.1 77.1 95.0 50 E1FW 1RA PVC21 0.95
63S M63 15.0 2″ 26.9 2 ½” 40.1 49.9 45.6 59.4 2.0 2.5 75.0 82.5 102.0 63S E1FW 1RA PVC23 1.34
63 M63 15.0 2 ½” 39.9 3″ 47.2 55.9 54.6 65.8 2.0 2.5 80.0 88.0 104.0 63 E1FW 1RA PVC25 1.34
75S M75 15.0 2 ½” 39.9 3″ 52.8 61.9 59.0 72.0 2.0 2.5 90.0 99.0 115.0 75S E1FW 1RA PVC28 2.11
75 M75 15.0 3″ 41.5 3 ½” 59.1 67.9 66.7 78.4 2.5 3.0 100.0 110.0 117.0 75 E1FW 1RA PVC30 2.42
90 M90 24.0 3 ½” 42.8 4″ 66.6 78.6 76.2 90.3 3.2 4.0 114.3 125.4 147.0 90 E1FW 1RA PVC32 4.21
100 M100 24.0 3 ½” 42.8 4″ 76.0 90.9 86.1 101.4 3.2 4.0 123.0 135.3 140.0 100 E1FW 1RA LSF33 4.45
115 M115 24.0 4″ 44.0 5″ 86.0 97.9 101.5 110.2 3.2 4.0 133.4 146.7 162.0 115 E1FW 1RA LSF34 6.19
130 M130 24.0 5″ 46.8 97.0 114.9 110.2 123.2 3.2 4.0 152.4 167.6 174.0 130 E1FW 1RA LSF35 8.34
Dimensions displayed in millimeters unless otherwise stated

Imperial

Cable Gland Size Available Entry Threads “C” (Alternate Metric Thread Lengths Available) Cable Bedding Diameter “A” Overall
Cable
Diameter
“B”
Armour Range Across
Flats
“D”
Across
Corners
“D”
Protrusion
Length “F”
Combined Ordering Reference
(*Brass Metric)
Shroud Cable
Gland
Weight
(Ozs)
Standard Option
Metric Thread Length (Metric) “E” NPT Thread Length
(NPT) “E”
NPT Min Max Min Max Min Max Max Max Size Type Ordering
Suffix
20S16 M20 0.59 ½” 0.78 ¾” 0.12 0.34 0.24 0.52 0.03 0.05 0.94 1.04 2.85 20S16 E1FW 1RA PVC04 5.64
20S M20 0.59 ½” 0.78 ¾” 0.24 0.46 0.37 0.63 0.03 0.05 0.94 1.04 2.76 20S E1FW 1RA PVC04 5.29
20 M20 0.59 ½” 0.78 ¾” 0.26 0.55 0.49 0.82 0.03 0.05 1.20 1.32 2.87 20 E1FW 1RA PVC06 7.41
25S M25 0.59 ¾” 0.80 1″ 0.44 0.78 0.55 0.87 0.05 0.06 1.48 1.63 3.50 25S E1FW 1RA PVC09 11.64
25 M25 0.59 ¾” 0.80 1″ 0.44 0.78 0.72 1.03 0.05 0.06 1.48 1.63 3.50 25 E1FW 1RA PVC09 11.64
32 M32 0.59 1″ 0.98 1 ¼” 0.67 1.03 0.93 1.33 0.06 0.08 1.81 1.99 3.39 32 E1FW 1RA PVC11 15.17
40 M40 0.59 1 ¼” 1.01 1 ½” 0.87 1.26 1.10 1.59 0.06 0.08 2.17 2.38 3.54 40 E1FW 1RA PVC15 21.87
50S M50 0.59 1 ½” 1.03 2″ 1.16 1.50 1.39 1.84 0.08 0.10 2.36 2.60 3.58 50S E1FW 1RA PVC18 26.46
50 M50 0.59 2″ 1.06 2 ½” 1.40 1.73 1.59 2.09 0.08 0.10 2.76 3.04 3.74 50 E1FW 1RA PVC21 33.51
63S M63 0.59 2″ 1.06 2 ½” 1.58 1.96 1.80 2.34 0.08 0.10 2.95 3.25 4.02 63S E1FW 1RA PVC23 47.27
63 M63 0.59 2 ½” 1.57 3″ 1.86 2.20 2.15 2.59 0.08 0.10 3.15 3.46 4.09 63 E1FW 1RA PVC25 47.27
75S M75 0.59 2 ½” 1.57 3″ 2.08 2.44 2.32 2.83 0.08 0.10 3.54 3.90 4.53 75S E1FW 1RA PVC28 74.43
75 M75 0.59 3″ 1.63 3 ½” 2.33 2.67 2.63 3.09 0.10 0.12 3.94 4.33 4.61 75 E1FW 1RA PVC30 85.36
90 M90 0.94 3 ½” 1.69 4″ 2.62 3.09 3.00 3.56 0.12 0.16 4.50 4.94 5.79 90 E1FW 1RA PVC32 148.50
100 M100 0.94 3 ½” 1.69 4″ 2.99 3.58 3.39 3.99 0.12 0.16 4.84 5.33 5.51 100 E1FW 1RA LSF33 156.97
115 M115 0.94 4″ 1.73 5″ 3.39 3.85 4.00 4.34 0.12 0.16 5.25 5.78 6.38 115 E1FW 1RA LSF34 218.35
130 M130 0.94 5″ 1.84 3.82 4.52 4.34 4.85 0.12 0.16 6.00 6.60 6.85 130 E1FW 1RA LSF35 294.19
Dimensions displayed in inches unless otherwise stated

Download Spec Sheet

Download

Technical

Design Specification BS 6121:Part 1:1989, IEC 62444, EN 62444
Mechanical Classifications* Impact = Level 8, Retention = Class D
Enclosure Protection IK10 to IEC 62262 (20 joules) Brass & Stainless Steel only
Electrical Classifications * Category B
ATEX Certificate SIRA13ATEX1071X, SIRA13ATEX4077X
Code of Protection II 2G, II 1D, Ex d IIC Gb, Ex e IIC Gb, Ex ta IIIC Da
II 3G Ex nR IIC Gc, IM2 Ex d I Mb, Ex e I Mb
Compliance Standards EN 60079-0,1,7,15,31
IECEx Certificate IECEx SIR 13.0026X, IECEx SIM 14.0007X
Code of Protection Ex d IIC Gb, Ex e IIC Gb, Ex nR IIC Gc, Ex ta IIIC Da, Ex d I Mb, Ex e I Mb
Compliance Standards IEC 60079-0,1,7,15,31
cCSAus Certificate 1310517
Code of Protection Ex d IIC; Ex e II; Ex nR II; Class I, Div 2, Groups A,B,C,D, Class II, Div 2 Groups E,F,G, Class
III, Encl Type T4X Class I, Zone 1, AEx e II / AEx nR II
Compliance Standards CAN/CSA-C22.2 No 0,18,25,30,174,94, CAN/CSA-E60079-0,1,7,15
ANSI/UL 514B Ed 5, ANSI/UL 50 Ed 11, ANSI/UL 2225 Ed 4, UL60079-0,1,7,15
EAC Certificate (Formerly GOST R, K & B) C-GB.AA87.B.00487
KCC Certificate 14-GA4BO-0257X
CCOE / PESO (India) Certificate P333688
NEPSI Certificate GYJ13.1140X , GYJ13.1282X
INMETRO Approval TÜV 12.0618X
RETIE Approval 03866
Marine Approvals LRS: 01/00172, DNV: E-13848, ABS: 14-LD234401A-4-PDA, BV: 43180/A1BV
Ingress Protection Rating ** IP66 as standard (IP67, IP68 available upon request)
Deluge Protection Compliance DTS01:91 option available on request (white ferrule for identification purposes)
Cable Gland Material Brass, Electroless Nickel Plated Brass, Aluminium
Seal Material CMP SOLO LSF Halogen Free Thermoset Elastomer
Cable Type Single Wire Armour (SWA), Aluminium Wire Armour (AWA)
Armour Clamping Detachable Armour Cone & AnyWay Universal Clamping Ring
Sealing Technique CMP Inner Displacement Seal & Unique CMP ‘LRS’ ™ Outer Load Retention Seal
Sealing Area(s) Cable Inner Bedding & Outer Cable Sheath
Optional Accessories Locknuts, Earth Tags, Serrated Washers, Entry Thread Seals, Shrouds,Ingress Discs
Optional Installation Tools Spanners, Armour Former Tool

Product Table

Metric

Cable Gland Size Available Entry Threads “C” (Alternate Metric Thread Lengths Available) Cable Bedding Diameter “A” Overall
Cable
Diameter
“B”
Armour Range Across
Flats
“D”
Across
Corners
“D”
Protrusion
Length “F”
Combined Ordering Reference
(*Brass Metric)
Shroud Cable
Gland
Weight
(Kgs)
Standard Option
Metric Thread Length (Metric) “E” NPT Thread Length
(NPT) “E”
NPT Min Max Min Max Min Max Max Max Size Type Ordering
Suffix
20S16 M20 15.0 ½” 19.9 ¾” 3.1 8.6 6.1 13.1 0.8 1.3 24.0 26.4 72.5 20S16 E1FW 1RA PVC04 0.16
20S M20 15.0 ½” 19.9 ¾” 6.1 11.6 9.5 15.9 0.8 1.3 24.0 26.4 70.0 20S E1FW 1RA PVC04 0.15
20 M20 15.0 ½” 19.9 ¾” 6.5 13.9 12.5 20.9 0.8 1.3 30.5 33.6 73.0 20 E1FW 1RA PVC06 0.21
25S M25 15.0 ¾” 20.2 1″ 11.1 19.9 14.0 22.0 1.3 1.6 37.5 41.3 89.0 25S E1FW 1RA PVC09 0.33
25 M25 15.0 ¾” 20.2 1″ 11.1 19.9 18.2 26.2 1.3 1.6 37.5 41.3 89.0 25 E1FW 1RA PVC09 0.33
32 M32 15.0 1″ 25.0 1 ¼” 17.0 26.2 23.7 33.9 1.6 2.0 46.0 50.6 86.0 32 E1FW 1RA PVC11 0.43
40 M40 15.0 1 ¼” 25.6 1 ½” 22.0 32.1 27.9 40.4 1.6 2.0 55.0 60.5 90.0 40 E1FW 1RA PVC15 0.62
50S M50 15.0 1 ½” 26.1 2″ 29.5 38.1 35.2 46.7 2.0 2.5 60.0 66.0 91.0 50S E1FW 1RA PVC18 0.75
50 M50 15.0 2″ 26.9 2 ½” 35.6 44.0 40.4 53.0 2.0 2.5 70.1 77.1 95.0 50 E1FW 1RA PVC21 0.95
63S M63 15.0 2″ 26.9 2 ½” 40.1 49.9 45.6 59.4 2.0 2.5 75.0 82.5 102.0 63S E1FW 1RA PVC23 1.34
63 M63 15.0 2 ½” 39.9 3″ 47.2 55.9 54.6 65.8 2.0 2.5 80.0 88.0 104.0 63 E1FW 1RA PVC25 1.34
75S M75 15.0 2 ½” 39.9 3″ 52.8 61.9 59.0 72.0 2.0 2.5 90.0 99.0 115.0 75S E1FW 1RA PVC28 2.11
75 M75 15.0 3″ 41.5 3 ½” 59.1 67.9 66.7 78.4 2.5 3.0 100.0 110.0 117.0 75 E1FW 1RA PVC30 2.42
90 M90 24.0 3 ½” 42.8 4″ 66.6 78.6 76.2 90.3 3.2 4.0 114.3 125.4 147.0 90 E1FW 1RA PVC32 4.21
100 M100 24.0 3 ½” 42.8 4″ 76.0 90.9 86.1 101.4 3.2 4.0 123.0 135.3 140.0 100 E1FW 1RA LSF33 4.45
115 M115 24.0 4″ 44.0 5″ 86.0 97.9 101.5 110.2 3.2 4.0 133.4 146.7 162.0 115 E1FW 1RA LSF34 6.19
130 M130 24.0 5″ 46.8 97.0 114.9 110.2 123.2 3.2 4.0 152.4 167.6 174.0 130 E1FW 1RA LSF35 8.34
Dimensions displayed in millimeters unless otherwise stated

Imperial

Cable Gland Size Available Entry Threads “C” (Alternate Metric Thread Lengths Available) Cable Bedding Diameter “A” Overall
Cable
Diameter
“B”
Armour Range Across
Flats
“D”
Across
Corners
“D”
Protrusion
Length “F”
Combined Ordering Reference
(*Brass Metric)
Shroud Cable
Gland
Weight
(Ozs)
Standard Option
Metric Thread Length (Metric) “E” NPT Thread Length
(NPT) “E”
NPT Min Max Min Max Min Max Max Max Size Type Ordering
Suffix
20S16 M20 0.59 ½” 0.78 ¾” 0.12 0.34 0.24 0.52 0.03 0.05 0.94 1.04 2.85 20S16 E1FW 1RA PVC04 5.64
20S M20 0.59 ½” 0.78 ¾” 0.24 0.46 0.37 0.63 0.03 0.05 0.94 1.04 2.76 20S E1FW 1RA PVC04 5.29
20 M20 0.59 ½” 0.78 ¾” 0.26 0.55 0.49 0.82 0.03 0.05 1.20 1.32 2.87 20 E1FW 1RA PVC06 7.41
25S M25 0.59 ¾” 0.80 1″ 0.44 0.78 0.55 0.87 0.05 0.06 1.48 1.63 3.50 25S E1FW 1RA PVC09 11.64
25 M25 0.59 ¾” 0.80 1″ 0.44 0.78 0.72 1.03 0.05 0.06 1.48 1.63 3.50 25 E1FW 1RA PVC09 11.64
32 M32 0.59 1″ 0.98 1 ¼” 0.67 1.03 0.93 1.33 0.06 0.08 1.81 1.99 3.39 32 E1FW 1RA PVC11 15.17
40 M40 0.59 1 ¼” 1.01 1 ½” 0.87 1.26 1.10 1.59 0.06 0.08 2.17 2.38 3.54 40 E1FW 1RA PVC15 21.87
50S M50 0.59 1 ½” 1.03 2″ 1.16 1.50 1.39 1.84 0.08 0.10 2.36 2.60 3.58 50S E1FW 1RA PVC18 26.46
50 M50 0.59 2″ 1.06 2 ½” 1.40 1.73 1.59 2.09 0.08 0.10 2.76 3.04 3.74 50 E1FW 1RA PVC21 33.51
63S M63 0.59 2″ 1.06 2 ½” 1.58 1.96 1.80 2.34 0.08 0.10 2.95 3.25 4.02 63S E1FW 1RA PVC23 47.27
63 M63 0.59 2 ½” 1.57 3″ 1.86 2.20 2.15 2.59 0.08 0.10 3.15 3.46 4.09 63 E1FW 1RA PVC25 47.27
75S M75 0.59 2 ½” 1.57 3″ 2.08 2.44 2.32 2.83 0.08 0.10 3.54 3.90 4.53 75S E1FW 1RA PVC28 74.43
75 M75 0.59 3″ 1.63 3 ½” 2.33 2.67 2.63 3.09 0.10 0.12 3.94 4.33 4.61 75 E1FW 1RA PVC30 85.36
90 M90 0.94 3 ½” 1.69 4″ 2.62 3.09 3.00 3.56 0.12 0.16 4.50 4.94 5.79 90 E1FW 1RA PVC32 148.50
100 M100 0.94 3 ½” 1.69 4″ 2.99 3.58 3.39 3.99 0.12 0.16 4.84 5.33 5.51 100 E1FW 1RA LSF33 156.97
115 M115 0.94 4″ 1.73 5″ 3.39 3.85 4.00 4.34 0.12 0.16 5.25 5.78 6.38 115 E1FW 1RA LSF34 218.35
130 M130 0.94 5″ 1.84 3.82 4.52 4.34 4.85 0.12 0.16 6.00 6.60 6.85 130 E1FW 1RA LSF35 294.19
Dimensions displayed in inches unless otherwise stated